BlueWalker VFI 10000T LCD Specifications

Browse online or download Specifications for Uninterruptible power supplies (UPSs) BlueWalker VFI 10000T LCD. BlueWalker PowerWalker VFI 6000T LCD User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Online UPS

Online UPS PowerWalker VFI 6000T LCD (L) PowerWalker VFI 10000T LCD (L) Manual (EN) Uninterruptible Power Supply System

Page 2

7  Outstanding adaptability to the worst mains input condition. Extra wide input voltage, frequency range and waveform, avoid excessive diss

Page 3

8 Wave form sinusoidal Load type PF 0.5~1, lagging THDV < 2% @ full linear load <5% @ full non linear load Overload In Line mode**: 10 min 1

Page 4 - 1.1 Installation

9 3.4 Typical Backup Time (Typical values at 25°C in minutes) Model No. 100 % Load PowerWalker VFI 6000T LCD 5 PowerWalker VFI 10000T LCD 4 3.5

Page 6 - 1.5 Storage

11 4. Installation 4.1 Moving to The Installation Site The series UPS has wheels making it easy to move the UPS to the installation site after

Page 7 - 1.6 Standards

12 2. Check all packaging materials to ensure that no items are missing. The shipping package contains: ● A UPS ● A user manual ● A USB cable

Page 8

13 4.3.2 Installation Use cable cross section and protective device specification Model PowerWalker VFI 6000T LCD (L) PowerWalker VFI 10000T LCD

Page 9 - 3. Introduction

14 BQ TUPSLNB Coil Remote SwitchQ Input Main BreakerT AC contactorN NeutralL Line inputMains input Fig.4-6 Typical external isolating

Page 10

15 8) Connect other input and output wires to the corresponding input and output terminals according to the following diagram. 9) It is requested t

Page 11 - 3.3 Operating Environment

16 14) If it is necessary to connect the inductance load such as a monitor or a laser printer to the UPS, the start-up power should be use

Page 12 - 3.5 Dimensions and Weights

CONTENT: 1. Safety and EMC Instructions ... 1 1.1 Installation ...

Page 13 - 10000T LCD (L)

17 3) Set the external battery pack breaker in “OFF” position and connect the 20 pieces of batteries in series. 4) Connect the external batte

Page 14 - 4. Installation

18 5. Operation 5.1 Display Panel The UPS has a four-button dot matrix LCD with dual color backlight. Standard back-light is used to light up the d

Page 15 - Ground Installation

19 Enter main menu When displaying default UPS status summary screen, press this button for >1s to enter the main menu tree Exit m

Page 16 - 6000T LCD (L)

20 Note: ●: Lightened constantly △ : #1-#4 Lightened circularly ★: Flashing ↑: Depended on the fault/warning status or othe

Page 17 - B Coil Remote Switch

21 Input220 V60 HzOutput220 V60 Hz5400 W273.0 V100%Utility input informationUPS output informationLoad informationBattery informationUPS operating st

Page 18

22 5.2.2 Battery mode The example of LCD display in battery mode is shown in the following diagram. Input0 V 0 HzOutput220 V60 Hz5400 W2

Page 19 - Battery (Only for “S” model)

23 5.2.4 Bypass without output The LCD display in bypass mode without output is shown in the following diagram. Input220 V60 HzOutput0 V 0 H

Page 20 - 4.5 EPO Connection

24 2) It is attention that the transfer time of UPS output from HE mode to battery mode is about 10ms. But it is still too long for some

Page 21 - 5. Operation

25 Input220 V60 HzOutput220 V60 Hz5400 W273.0 V100%The symbol of Warning Fig. 5-9 Warning 5.2.8 Fault When the fault occurs, it illustrates th

Page 22

26 Input220 V60 HzOutput220 V60 Hz6480 W273.0 V120%The symbol of overload Fig. 5-11 Overload While doing the battery test, LEDs would be lighted cir

Page 23

8. Battery Maintenance ... 51 9. Communication Port ...

Page 24 - 5.2 Operating Mode

27 5.3 Turning On and Turning Off UPS Attention: The UPS could only be turning on while connecting with the mains at the first time. Attention: Ple

Page 25

28 5.3.3 Turning off UPS with mains 1) To turn off the inverter of UPS by pressing button continuously for more than 3s and the buzzer wi

Page 26

29 Fig. 5-14 Main menu tree WELCOMEAlarm # 41Battery Volt: 220VBattery chargingCharger level:100%Status:Para

Page 27

30 5.4.2 The UPS status menu By pressing on the menu of “UPS status”, the display would enter the next UPS status menu tree. The content

Page 28 - The symbol of Fault

31 5.4.3 The event log menu By pressing on the menu of “Event log”, the display would enter the next event menu tree. All the old event, alarm

Page 29 - The symbol of battery failure

32 5.4.4 The measurement menu By pressing on the menu of “Measurement”, the display would enter the next measurement menu tree. A lot of detailed

Page 30

33 5.4.5 The control menu By pressing on the menu of “Control”, the display would enter the next control menu tree. 1) Single UPS turn off: is on

Page 31 - 5.4 LCD Operation

34 Fig. 5-18 Control menu tree

Page 32

35 Example: clear EPO status Clear EPO statusBy press <1sStatus:EPO activeClear:noStatus:EPO activeClear:yesBy press or &

Page 33

36 Fig. 5-20 Identification menu tree 5.4.7 The setting menu Please contact your local distributor for further information before using the settings

Page 34

1 1. Safety and EMC Instructions Please read carefully the following user manual and the safety instructions before installing the unit or using t

Page 35

37 Fig. 5-21 Setting menu tree By press on the menu of “Identification”, the display would enter the next setti

Page 36

38 Table 5-4 Submenu item Optional Values Default value User password enabled/disabled disabled Audio alarm enabled/disabled enabled Rated output vol

Page 37

39 Example: set rated output voltage value Output voltage<230V>...By press or <1sThe option would flashOutput voltage<230

Page 38 - By press >1s

40 6. Special Function The series UPS has some special functions, which could satisfy some special application of user. And the funct

Page 39

41 6.2 Converter Function 6.2.1 Brief introduction of Converter function In converter mode, the UPS would free run with fixed output freque

Page 40

42 6.3.2 Parallel installation and operation How to install a new parallel UPS system: 1) Before installing a new parallel UPS system, user

Page 41 - permanently

43 IP_G IP_N IP_L B+ B- B_G J1 J2 OP_N OP_L OP_GIP_G IP_N IP_L B+ B-

Page 42

44 Fig. 6-2 Parallel System Installation Diagram 10) Do not switch on the output breaker of each UPS, switch on the input breaker of the each UPS,

Page 43 - 6. Special Function

45 13) Press the button of one UPS, each UPS would start to turn on, after turning on, the UPSs should work parallel in the Line mode. How to joi

Page 44 - 6.3 Parallel Function

46 automatically, set the own maintenance switch of each UPS from “UPS” to “BPS”. 3) Set the main maintenance switch or static switch fro

Page 45

2  With the installation of the equipment, the sum of the leakage current of the UPS and the connected load does not exceed 5% of rated value of in

Page 46 - TO UTILITY

47 7. Trouble Shooting If the UPS system does not operate correctly, first check the operating information on the LCD display. Please attempt to

Page 47

48 Over Charge Battery is over charged The UPS will turn off the charger until the battery voltage is normal Model Pin Error UPS internal fault Con

Page 48

49 7.2 Trouble Shooting According To Fault Indication Problem Displayed Possible cause Remedy Inv Overload Fault Overload Check the loads and rem

Page 49

50 7.3 Trouble Shooting In Else Cases Problem Possible cause Remedy No indication, no warning tone even though system is connected to mains power sup

Page 50 - 7. Trouble Shooting

51 8. Battery Maintenance Battery replacement should be performed by qualified personnel.  This series UPS only requires minimal maintenance

Page 51

52 9. Communication Port 9.1 USB Interface The USB port is compliance with USB 1.1 protocol for its communication software. 9.2 Dry contact Interfa

Page 52

53 RS-232 communication port pin assignments Pin Signal name Function Direction from the UPS 1 Unused Not applicable 2 Tx Transmit to external devic

Page 53

54 10. Software Installation WinPower is UPS monitoring software, featuring user-friendly interface to monitor and control your UPS. This unique soft

Page 55 - 9. Communication Port

3  Before carrying out any kind of service and/or maintenance, isolate UPS and disconnect the batteries. Verify that no current is present

Page 56 - 9.4 Intelligent slot

4 1.6 Standards * Safety IEC/EN 62040-1 * EMI Conducted Emission...:IEC/EN 62040-2 Category C3 Radiated Emission...

Page 57 - 10. Software Installation

5 2. Description of Commonly Used Symbols Some or all of the following symbols may be used in this manual. It is advisable to familiarize yourself

Page 58 - 614-09335-00

6 3. Introduction This On-Line series is an uninterruptible power supply incorporating double-converter technology. It provides perfect protection s